danfoss a60 alarm
Common Causes & Troubleshooting
The "External Interlock" is essentially a "permission to run" signal. If the drive loses the 24V signal on the terminal assigned to this function, it trips.
Open Safety Device: Check any external devices wired to the drive, such as:
Fire/Smoke detectors or Fire Alarms.
High/Low pressure switches.
Emergency Stop (E-Stop) buttons.
Freezestats (in HVAC applications).
Loose Wiring: Check for loose or broken wires on the control terminals.
Blown Fuse/Power Loss: If your 24V supply is shorted or failing, the drive won't see the signal and will trigger the alarm.
- Incorrect Programming: If you aren't using an external interlock but the drive is programmed to look for one, it will trip by default.
How to Fix / Reset
Check the Safety Circuit: Ensure all external sensors are in their "normal" state. If a pressure switch has tripped, you must fix the mechanical issue first.
Verify Voltage: Use a multimeter to check for 24V DC between the Common (Terminal 12) and the Interlock Input.
Note: If you are testing and want to bypass this for troubleshooting, you can install a temporary jumper wire between 24V and digital input.
Clear the Alarm: Once the 24V signal is restored, press the [Reset] button on the drive keypad (LCP).

Comments
Post a Comment