earth fault 2 a45 danfoss

In Danfoss VFD, Alarm 45 (Earth Fault 2) is a critical safety trip. While Alarm 14 is a general ground fault that can happen at any time, Alarm 45 specifically occurs during the start-up sequence (when the drive is performing a pre-start check of the motor circuits).

It indicates that a leakage current is flowing from the output phases to the ground, usually due to a breakdown in insulation in the motor or the cabling.

earth fault 2 a45 danfoss

 


Primary Causes

  • Insulation Breakdown: The most common cause is moisture or heat damage in the motor windings or the motor power cable.

  • Moisture in Terminal Box: Water or heavy condensation inside the motor’s electrical junction box.

  • Cable Damage: A nicked or crushed motor cable where a conductor is touching the conduit or earth.

  • Current Sensor Offset: Over time, the internal sensors can develop an "offset" (drift), making the drive think there is a leak when there isn't.


Troubleshooting Steps

1. Megger the Motor and Cable

The most effective way to find a real ground fault is using an insulation resistance tester (Megger).

  • Isolate the Drive: Disconnect the motor cables from the VFD terminals (U, V, W). Never Megger into the drive itself, as you will destroy the power electronics.

  • Test Phases to Ground: Test each lead (U-Gnd, V-Gnd, W-Gnd). A healthy motor and cable should typically read well above 500 MΩ. If it is below 2 MΩ, you have a confirmed fault.

2. Test the Drive "Open"

To rule out an internal drive failure:

  • With the motor cables still disconnected, try to start the drive.

  • If the drive stays in "Running" mode (or gives a "Missing Motor Phase" alarm instead of Alarm 45), the drive is healthy, and the fault is definitely in your cable or motor.

  • If Alarm 45 returns even with no motor connected, the internal current sensors or the power card have failed.

3. Perform a Manual Initialization (Current Sensor Reset)

If the motor tests fine, the sensors might just need recalibration.

  • Power off the drive.

  • Hold [Status], [Main Menu], and [OK] while powering the drive back on.

  • This resets all parameters to factory defaults and forces the drive to recalibrate its zero-current offsets.

  • Note: You will need to re-enter your motor nameplate data after this.

4. Check for Moisture

If the system has been sitting idle in a damp environment, run the "Motor Preheat" function if available, or use a space heater to dry out the motor junction box and windings.


Summary Table

Result of Megger TestLikely IssueAction
Low Resistance (< 2 MΩ)Grounded Motor or CableInspect cable runs and motor windings.
High Resistance (> 10 MΩ)Drive Sensor DriftPerform Manual Initialization.
Alarm 45 with motor disconnectedInternal Drive HardwareReplace Control Card or Power Card.

Comments