What is f0001 fault in abb drive?

F0001 fault in an
ABB drive indicates an overcurrent trip, meaning the motor current has exceeded the drive's internal threshold, usually due to excessive load, short circuits in the motor/cables, or damaged internal hardware.

f0001 fault in abb drive

 

Causes for f0001 fault in abb drive:

  • Excessive Load: The motor is overloaded or jammed mechanically.
  • Short Circuit: Short circuit in the motor cable(s) or the motor itself.
  • Acceleration Time: Acceleration time is too short.
  • Internal Damage: Damaged IGBT modules or internal hardware

Solution:

  • Disconnect the motor cable from the VFD and attempt to run the drive. If the F0001 fault persists, the drive's internal hardware is damaged and likely requires professional repair.
  • If the fault disappears with the motor disconnected, inspect the motor and cable for short circuits or insulation issues.
  • Check for acceleration time (\(t_{acc}\)) settings—too short can cause overcurrent.
  • Verify if the motor is stalled or experiencing a mechanical blockage 