f1 fault in siemens v20

Siemens V20 F1 fault signifies Overcurrent, meaning the drive detected current exceeding safe limits, often due to mechanical issues, motor mismatches, or electrical problems like short circuits/ground faults.

f1 fault in siemens v20

 

 Causes for f1 fault in siemens v20:

  • Motor/Inverter Mismatch: Motor power rating (P0307) doesn't match the inverter's (r0206).
  • Mechanical Issues: Motor is overloaded, obstructed, or has a short circuit/earth fault.
  • Cable Problems: Motor cables are too long or have ground faults.
  •  Incorrect Parameters: Motor parameters (like stator resistance P0350) are wrong.
  • High Starting Torque: The motor needs more torque to start, causing a current spike. 

 Solutions:

  • Check Motor & Cables: Verify motor power matches inverter, inspect cables for shorts/ground faults, and check for obstructions/overloading.
  • Verify Parameters: Ensure motor parameters, especially stator resistance (P0350), are correct for the connected motor.
  • Adjust Ramps: Increase the ramp-up time (P1120) to give the motor more time to accelerate.
  • Reduce Starting Boost: Lower the starting boost level (P1312) if the motor struggles to start.
  • Check External Load: Observe the machine when the fault occurs to identify mechanical binding or excessive load. 

Comments