EF (EF1, EF2) Earth Fault / Ground Fault fault in Toshiba drive

EF (EF1, EF2) Earth Fault / Ground Fault fault in Toshiba drive

Description An EF fault occurs when the drive detects current leakage from the output phases to the earth (ground). The drive uses a Zero Phase Sequence Current Transformer (ZCT) or software calculation to sum the currents of U, V, and W. Under normal conditions, the sum should be zero. If current leaks to the ground, the sum is non-zero. This is a critical safety fault indicating damaged insulation. Resetting this fault repeatedly without fixing the cause will destroy the drive. Causes
1. Motor Insulation Failure: The varnish on the motor copper windings has burned off, shorting to the motor stator/frame.
2. Cable Damage: The output cable insulation has been chafed, cut, or soaked in water (conduit flooding).
3. Moisture: Water ingress in the motor terminal box or the VFD terminal strip.
4. Long Cable Runs: Extremely long motor cables can create capacitive leakage to the ground that the drive misinterprets as a short. Solution DO NOT RESET AND RUN. You must verify the insulation integrity.

1. Disconnect the motor cables (U, V, W) from the VFD output terminals.
2. Use an Insulation Resistance Tester (Megger) set to 500V or 1000V.
3. Test each motor cable phase to Ground. The reading should be high (ideally >50 Mega-Ohms). If the reading is close to 0 or below 1 Mega-Ohm, you have a dead short to ground.
4. If the cable and motor test fine, reconnect the wires and try to run. If it trips EF immediately with good motor insulation, the fault might be internal to the drive (faulty current sensors), requiring drive replacement.

If you have very long motor cables (over 100 meters), the stray capacitance might be tripping the EF protection. In this case, you may need to reduce the Carrier Frequency (switching frequency) to reduce leakage current, or install a dV/dt filter or Output Reactor. In rare diagnostic cases, you can temporarily disable the "Ground Fault Detect" parameter to see if the drive runs, but this removes safety protection and risks fire if a real fault exists.

Comments