Fault 7510 in ABB ACS800 drive

Fault 7510 in ABB ACS800 drive indicates a COMM MODULE fault. This means loss of cyclic communication between the drive and the fieldbus master (PLC).

Fault 7510 in ABB ACS800 drive


Why is this happening?

Before you start swapping out expensive parts, let’s look at the usual suspects:

  • Cable Issues: A loose connector, a crimped fiber optic cable, or electromagnetic interference (EMI) disrupting the signal.

  • Module Seat: The fieldbus adapter might not be seated properly in its slot on the RMIO board.

  • Timeouts: The "Comm Loss Timeout" setting in the drive is too aggressive for the network traffic.

  • PLC State: The Master PLC might be in 'Stop' mode or the network itself has crashed. 

Troubleshooting Checklist

StepActionWhat to look for
1Check the LEDsLook at the Fieldbus module. If the "Link" light is off or "Host" is red, the module isn't talking to the drive.
2Verify Parameter 30.18Check the COMM FAULT FUNC. If it’s set to "FAULT," the drive trips. You can change this to "CONSTANT SP 15" for testing to see if the drive keeps running.
3Check Parameter 30.19This is the COMM FAULT TIME. If it’s set to 0.1s, it might be too fast. Try increasing it to 1.0s to see if the fault clears.
4Inspect WiringEnsure the termination resistors are "ON" at the ends of the physical segment and "OFF" everywhere else.