SLF1 Slot 1 Card Fault fault in delta drive
SLF1 Slot 1 Card Fault fault in delta drive troubleshooting
Description
Delta C2000/CP2000 drives have expansion slots for option cards (Encoder cards, Communication cards, I/O cards). SLF1 indicates a communication loss or hardware failure with the card installed in Slot 1 (usually the communication slot).
Causes
1. Poor Connection: The card is not seated firmly in the header socket.
2. Card Failure: The option card itself is damaged.
3. Interference: High electrical noise is disrupting the internal SPI bus between the drive CPU and the option card.
4. Incompatible Card: Using an old version card on a new firmware drive.
Solution
Reseat and check:
1. Power Down: Never remove cards while powered. Turn off power completely.
2. Reseat Card: Unplug the card, check pins for bending, and plug it back in firmly. Secure it with the screw.
3. Grounding: Ensure the drive chassis is grounded to earth to prevent internal noise.
4. Swap Slots: If possible, try moving the card to Slot 2 or Slot 3 to see if the fault changes to SLF2/SLF3 (indicating the card is bad) or stays SLF1 (indicating the drive slot is bad).