HVAC Drive H300 Drive Fault Codes
Complete guide to Nidec Control Techniques HVAC Drive H300 errors. Learn to troubleshoot Fire Mode, BACnet comms, OI.AC, and It.AC trips using the HOA keypad and Connect software.
H300 Fault Codes Reference Table
Below is the reference list of common trips and alarms for the HVAC Drive H300. The drive distinguishes between “Alarms” (which warn you of a developing issue) and “Trips” (which stop the motor to protect equipment).
HVAC Drive H300 - Trip Indications
| Fault Code and Meaning | Cause and Remedy |
|---|---|
| 28 An Input 1 Loss (Analog input 1 current loss) |
Cause: Current loss detected in current mode on Analog input 1 (Terminal 5, 6). In 4-20 mA and 20-4 mA modes, loss of input is detected if the current falls below 3 mA.
Remedy:
|
| 29 An Input 2 Loss (Analog input 2 current loss) |
Cause: Current loss detected in current mode on Analog input 2 (Terminal 7). In 4-20 mA and 20-4 mA modes, loss of input is detected if the current falls below 3 mA.
Remedy:
|
| 219 An Output Calib (Analog output calibration failed) |
Cause: The zero offset calibration of one or both of the analogue outputs has failed. Likely hardware failure or voltage applied to output via low impedance/wiring error.
Sub-trip 1: Output 1 failed (Terminal 9). Sub-trip 2: Output 2 failed (Terminal 10). Remedy:
|
| 217 App Menu Changed (Customization table changed) |
Cause: The customization table for an application menu has changed (Menu 18, 19, or 20). If more than one menu changed, the lowest menu has priority.
Remedy:
|
| 11 Autotune 1 (Position feedback or speed error) |
Cause: Tripped during autotune.
Sub-trip 1: Position feedback did not change during rotating autotune. Sub-trip 2: Motor did not reach required speed during rotating autotune or mechanical load measurement. Remedy:
|
| 12 Autotune 2 (Position feedback direction incorrect) |
Cause: Tripped during rotating autotune.
Sub-trip 1: Position feedback direction incorrect. Sub-trip 2: SINCOS encoder with comms used, position rotating opposite to sine wave based position. Remedy:
|
| 13 Autotune 3 (Measured inertia / Commutation signals) |
Cause: Tripped during rotating autotune or mechanical load measurement test.
Sub-trip 1: Measured inertia exceeded parameter range. Sub-trip 2: Commutation signals changed in wrong direction. Sub-trip 3: Mechanical load test unable to identify motor inertia. Remedy:
|
| 17 Autotune 7 (Motor poles / position feedback resolution) |
Cause: Initiated during rotating autotune if the motor poles or the position feedback resolution have been set up incorrectly.
Remedy:
|
| 18 Autotune Stopped (Stopped before completion) |
Cause: Prevented from completing autotune because either drive enable or drive run were removed.
Remedy:
|
| 19 Brake R Too Hot (Braking resistor overload timed out) |
Cause: Braking resistor overload timed out ($I^2t$). The trip is initiated when Braking Resistor Thermal Accumulator (10.039) reaches 100%.
Remedy:
|
| 185 Card Access (NV Media Card Write fail) |
Cause: Drive unable to access NV Media Card. File being written may be corrupted or transfer incomplete.
Remedy:
|
| 177 Card Boot (Menu 0 param modification not saved) |
Cause: Write to Menu 0 initiated but necessary boot file not created on NV Media Card. Occurs when Pr 11.042 changed to Auto or Boot mode but drive not reset.
Remedy:
|
| 178 Card Busy (NV Card accessed by option module) |
Cause: Attempt to access file on NV Media Card while it is already being accessed by an option module. No data transferred.
Remedy:
|
| 188 Card Compare (File/data different to drive) |
Cause: Compare carried out between file on NV Media Card and drive; parameters differ.
Remedy:
|
| 179 Card Data Exists (Location already contains data) |
Cause: Attempt made to store data in a block which already contains data.
Remedy:
|
| 187 Card Drive Mode (Parameter set not compatible) |
Cause: Drive mode in data block differs from current drive mode, or operating mode in data block is outside allowed range.
Remedy:
|
| 182 Card Error (NV Media Card data structure error) |
Cause: Error detected in data structure.
Sub-trip 1: Required folder/file structure not present. Sub-trip 2: The <000> file is corrupted. Sub-trip 3: Two or more files have same identification number. Remedy:
|
| 184 Card Full (NV Media Card full) |
Cause: Not enough space left on the card to create a data block.
Remedy:
|
| 183 Card No Data (NV Media Card data not found) |
Cause: Attempt made to access non-existent file or block on a NV Media Card.
Remedy:
|
| 180 Card Option (Option modules installed are different) |
Cause: Option module categories differ between source and destination drives. This is a warning; data for option modules different will be set to defaults.
Remedy:
|
| 175 Card Product (Data blocks not compatible with drive derivative) |
Cause: Drive Derivative (11.028) or Product Type (11.063) differ between source and target drives.
Sub-trip 1: Drive Derivative differs. Sub-trip 2: Product Type differs or file corruption. Sub-trip 3: Unidrive SP parameter value found with no equivalent. Remedy:
|
| 186 Card Rating (Voltage / current rating different) |
Cause: Current and/or voltage ratings are different between source and destination drives. Rating specific parameters may not be transferred.
Remedy:
|
| 181 Card Read Only (Read Only bit set) |
Cause: Attempt made to modify a read-only NV Media Card or read-only data block.
Remedy:
|
| 174 Card Slot (Option module application program transfer failed) |
Cause: Transfer of an option module application program failed because the option module did not respond correctly.
Remedy:
|
| 111 Configuration |
Cause: The number of power modules installed is different from the modules expected (Pr 11.071), or the number of external rectifiers (Pr 11.096) is incorrect.
Remedy:
|
| 35 Control Word |
Cause: Trip initiated from the Control Word. Bit 12 on the control word in Pr 06.042 was set when the control word was enabled (Pr 06.043 = On).
Remedy:
|
| 225 Current Offset |
Cause: Current feedback offset error. The current feedback offset is too large to be trimmed correctly.
Remedy:
|
| 97 Data Changing |
Cause: Drive parameters are being changed while the drive is active. Actions include loading defaults, changing drive mode, or transferring data from NV memory card.
Remedy:
|
| 247 Derivative ID |
Cause: There is a problem with the identifier associated with derivative image which customizes the drive.
Sub-trip 1: Image erased. Sub-trip 2: Identifier out of range. Sub-trip 3: Derivative image changed. Remedy:
|
| 248 Derivative Image |
Cause: Derivative Image error. An error has been detected in the derivative image.
See sub-trip codes (1-52, 61-64, 70-74, 80-81) for specific details regarding option slots or missing images. Remedy:
|
| 199 Destination |
Cause: Two or more parameters are writing to the same destination parameter.
Remedy:
|
| 224 Drive Size |
Cause: Power stage recognition: Unrecognized drive size. The control PCB has not recognized the drive size of the power circuit.
Remedy:
|
| 31 EEPROM Fail |
Cause: Default parameters have been loaded. The exact cause is identified by the sub-trip number (e.g., checksum failure, version change, CRC error).
Remedy:
|
| 197 Encoder 9 |
Cause: Position feedback is selected from an option module slot which does not have a feedback option module installed.
Remedy:
|
| 6 External Trip |
Cause: An External trip is initiated via Pr 10.038, Safe Torque Off input state, or Serial Comms.
Remedy:
|
| HF01 Data processing error: CPU address error |
Cause: The control PCB on the drive has failed (CPU address error).
Remedy:
|
| HF02 Data processing error: DMAC address error |
Cause: A DMAC address error has occurred. The control PCB has failed.
Remedy:
|
| HF03 Data processing error: Illegal instruction |
Cause: An illegal instruction has occurred. The control PCB has failed.
Remedy:
|
| HF04 Data processing error: Illegal slot instruction |
Cause: An illegal slot instruction has occurred. The control PCB has failed.
Remedy:
|
| HF05 Data processing error: Undefined exception |
Cause: An undefined exception error has occurred. The control PCB has failed.
Remedy:
|
| HF06 Data processing error: Reserved exception |
Cause: A reserved exception error has occurred. The control PCB has failed.
Remedy:
|
| HF07 Data processing error: Watchdog failure |
Cause: A watchdog failure has occurred. The control PCB has failed.
Remedy:
|
| HF08 Data processing error: CPU Interrupt crash |
Cause: A CPU interrupt crash has occurred. The control PCB has failed.
Remedy:
|
| HF09 Data processing error: Free store overflow |
Cause: A free store overflow has occurred. The control PCB has failed.
Remedy:
|
| HF10 Data processing error: Parameter routing system error |
Cause: A Parameter routing system error has occurred. The control PCB has failed.
Remedy:
|
| HF11 Data processing error: Access to EEPROM failed |
Cause: Access to the drive EEPROM has failed. The control PCB has failed.
Remedy:
|
| HF12 Data processing error: Main program stack overflow |
Cause: Main program stack overflow has occurred. The stack can be identified by the sub-trip number (1: Background tasks, 2: Timed tasks, 3: Main system interrupts). This indicates the control PCB has failed.
Remedy:
|
| HF13 Data processing error: Firmware incompatible with hardware |
Cause: The drive firmware is not compatible with the hardware. Indicates control PCB failure. Sub-trip gives the ID code of the board.
Remedy:
|
| HF14 Data processing error: CPU register bank error |
Cause: A CPU register bank error has occurred. Indicates control PCB failure.
Remedy:
|
| HF15 Data processing error: CPU divide error |
Cause: A CPU divide error has occurred. Indicates control PCB failure.
Remedy:
|
| HF16 Data processing error: RTOS error |
Cause: A RTOS error has occurred. Indicates control PCB failure.
Remedy:
|
| HF17 Data processing error: Clock supplied to control board out of spec |
Cause: The clock supplied to the control board logic is out of specification. Indicates control PCB failure.
Remedy:
|
| HF18 Data processing error: Internal flash memory has failed |
Cause: Internal flash memory failed when writing option module parameter data. Sub-trip identifies reason (e.g., Timeout, CRC errors).
Remedy:
|
| HF19 Data processing error: CRC check on firmware has failed |
Cause: The CRC check on the drive firmware has failed.
Remedy:
|
| HF20 Data processing error: ASIC is not compatible with the hardware |
Cause: The ASIC version is not compatible with the drive firmware.
Remedy:
|
| HF23 to HF25 Hardware fault |
Cause: General hardware failure detected.
Remedy:
|
| I/O Overload (Trip 26) Digital output overload |
Cause: Total current drawn from 24 V user supply or digital output exceeded limit (100 mA).
Remedy:
|
| Inductance (Trip 8) Motor inductances not suitable |
Cause: Occurs in RFC-S mode. The ratio or difference between Ld and Lq is too small, or saturation characteristic cannot be measured.
Remedy:
|
| Inter-connect (Trip 103) Multi-power module drive interconnection cable error |
Cause: A power module has detected a fault (sub-trip "xx.0.00" indicates module number). Initiated if communication fails, rectifier signals fault, or trip is reset.
Remedy:
|
| Keypad Mode (Trip 34) Keypad removed when drive receiving reference from keypad |
Cause: Drive is in keypad mode [Reference Selector (01.014) = 4 or 6] and keypad has been removed or disconnected.
Remedy:
|
| Motor Too Hot (Trip 20) Output current overload timed out (I2t) |
Cause: Motor thermal overload based on rated current (Pr 05.007) and motor thermal time constant. Trip occurs when accumulator reaches 100%.
Remedy:
|
| Name Plate (Trip 176) Electronic nameplate transfer has failed |
Cause: Electronic nameplate transfer between drive and motor failed. Reasons include: Not enough memory, Comms failed, or Checksum failed.
Remedy:
|
| OHt Brake (Trip 101) Braking IGBT over-temperature |
Cause: Braking IGBT over-temperature detected based on software thermal model.
Remedy:
|
| OHt Control (Trip 23) Control stage over temperature |
Cause: Control stage over-temperature detected. Sub-trip identifies location (01: Control board thermistor 1, 02: Control board thermistor 2, 03: I/O board thermistor).
Remedy:
|
| OHt dc bus (27) DC bus over temperature |
Cause:
A DC bus component over-temperature has been detected based on a software thermal model (includes effects of output current and DC bus ripple). Remedy:
|
| OHt Inverter (21) Inverter over temperature |
Cause:
An IGBT junction over-temperature has been detected based on a firmware thermal model. Remedy:
|
| OHt Power (22) Power stage over temperature |
Cause:
A power stage over-temperature has been detected (heatsink or specific power module components). Remedy:
|
| OI ac (3) Instantaneous output over current |
Cause:
Instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX. Remedy:
|
| OI Brake (4) Braking IGBT over current |
Cause:
Over current detected in braking IGBT or braking IGBT protection has been activated. Remedy:
|
| OI dc (109) Power module over current |
Cause:
Short circuit protection for the drive output stage has been activated (detected from IGBT on state voltage monitoring). Remedy:
|
| OI Snubber (92) Snubber over-current |
Cause:
Over-current condition detected in the rectifier snubber circuit. Remedy:
|
| Option Disable (215) Option module error |
Cause:
Option module does not acknowledge drive mode changeover within the allowed time. Remedy:
|
| Out Phase Loss (98) Output phase loss detected |
Cause:
A phase loss has been detected at the drive output (U, V, or W phase disconnected). Remedy:
|
| Over Speed (7) Motor speed exceeded threshold |
Cause:
Motor speed has exceeded the Over Speed Threshold (03.008). Can be caused by control loop overshoot or mechanical driving. Remedy:
|
| Over Volts (2) DC bus voltage exceeded limit |
Cause:
DC bus voltage has exceeded the peak level or maximum continuous level for 15 seconds. Remedy:
|
| 32 Phase Loss (Supply phase loss) |
Cause: Input phase loss or large supply imbalance detected. This can be detected directly from the supply or by monitoring the ripple in the DC bus voltage.
Remedy:
|
| 198 Phasing error |
Cause: The phase offset angle in Position Feedback Phase Angle (03.025 or 21.020) is incorrect, or position feedback is being used and the drive is unable to control the motor correctly.
Remedy:
|
| 90 Power Comms |
Cause: A communications problem within the power system of the drive (between Control system, Power module, or Rectifier module).
Remedy:
|
| 220 Power Data |
Cause: Error in the configuration data stored in the power system. This can be due to missing data tables, size mismatch, CRC errors, or version mismatch between generator software and table.
Remedy:
|
| 37 Power Down Save |
Cause: An error has been detected in the power down save parameters saved in non-volatile memory.
Remedy:
|
| 5 PSU (Internal power supply fault) |
Cause: One or more internal power supply rails are outside limits or overloaded (Control system overload or Rectifier internal overload).
Remedy:
|
| 9 PSU 24V (24V internal power supply overload) |
Cause: The total user load of the drive and option modules has exceeded the internal 24 V power supply limit (drive digital outputs and main encoder supply).
Remedy:
|
| 223 Rating Mismatch |
Cause: Voltage rating or current rating mismatch in a multi-module drive system. Modules connected in parallel must have the same frame size and rating.
Remedy:
|
| 94 Rectifier Set-up |
Cause: A rectifier has not been set-up correctly in a multi-power module system.
Remedy:
|
| 33 Resistance |
Cause: Measured stator resistance is too high, or an attempt to measure it failed. Can be caused by values exceeding the VFS/Full Scale Current ratio.
Remedy:
|
| 216 Slot App Menu |
Cause: Application menu Customization conflict error. More than one option slot has requested to customize application menus 18, 19, and 20.
Remedy:
|
| 204, 209, 214 SlotX Different |
Cause: Option module in option slot X on the drive is a different type to that installed when parameters were last saved on the drive.
Remedy:
|
| 202, 207, 212 SlotX Error |
Cause: The option module in option slot X on the drive has detected an error.
Remedy:
|
| 200, 205, 210 SlotX HF |
Cause: Option module X hardware fault. Possible causes include unidentified category, corrupt tables, insufficient memory, or communication failure.
Remedy:
|
| 203, 208, 213 SlotX Not Fitted |
Cause: The option module in option slot X has been removed since the last power up.
Remedy:
|
| 201, 206, 211 SlotX Watchdog |
Cause: The option module installed in Slot X has started the option watchdog function and then failed to service the watchdog correctly.
Remedy:
|
| 226 Soft Start |
Cause: The Soft Start trip indicates that the soft start relay in the drive failed to close or the soft start monitoring circuit has failed.
Remedy:
|
| 221 Stored HF |
Cause: The Stored HF trip indicates that a hardware trip (HF01 – HF19) has occurred and the drive has been power cycled. The sub-trip number identifies the HF trip.
Remedy:
|
| 227 Sub-array RAM |
Cause: The Sub-array RAM trip indicates that an option module, derivative image or user program image has requested more parameter RAM than is allowed. The failure with the highest sub-trip number is given.
Remedy:
|
| 218 Temp Feedback |
Cause: An internal thermistor has failed. The thermistor location can be identified by the sub-trip number (e.g., Control board thermistor, I/O board thermistor).
Remedy:
|
| 10 Th Brake Res |
Cause: The Th Brake Res is initiated if hardware based braking resistor thermal monitoring is connected and the resistor overheats.
Remedy:
|
| 25 Th Short Circuit |
Cause: This trip indicates that a temperature sensor connected to an analogue input or terminal 15 has a low impedance (i.e. < 50 Ω).
Remedy:
|
| 24 Thermistor |
Cause: The motor thermistor connected to terminal 8 (analog input 3) or terminal 15 (encoder) has indicated a motor over temperature.
Remedy:
|
| 110 Undefined |
Cause: The Undefined trip indicates that the power system has generated but did not identify the trip. The cause is unknown.
Remedy:
|
| 91 User 24V |
Cause: A User 24 V trip is initiated if User Supply Select is set to 1 or Low Under Voltage Threshold Select = 1 and no user 24 V supply is present on control terminals 1 and 2.
Remedy:
|
| 249 User Program |
Cause: An error has been detected in the onboard user program image. The reason can be identified by the sub-trip number (e.g., Divide by zero, Undefined trip, RAM allocation error).
Remedy:
|
| 96 User Prog Trip |
Cause: This trip can be initiated from within an onboard user program using a function call which defines the sub-trip number.
Remedy:
|
| 36 User Save |
Cause: An error has been detected in the user save parameters (e.g., power removed during save).
Remedy:
|
| 41-89 112-159 User Trip |
Cause: These trips are not generated by the drive and are to be used by the user to trip the drive through an application program.
Remedy:
|
| 30 Watchdog |
Cause: The control word watchdog has been enabled and has timed out.
Remedy:
|
| HF01 to HF20 Internal / Hardware trips |
Cause: Internal faults that do not have trip numbers. The main drive processor has detected an irrecoverable error. Remedy:
|
| Error 1 Programming Error |
Cause: There is not enough drive memory requested by all the option modules. Remedy:
|
| Error 2 Programming Error |
Cause: At least one option module did not acknowledge the reset request. Remedy:
|
| Error 3 Programming Error |
Cause: The boot loader failed to erase the processor flash. Remedy:
|
| Error 4 Programming Error |
Cause: The boot loader failed to program the processor flash. Remedy:
|
| Error 5 Programming Error |
Cause: One option module did not initialize correctly. Option module did not set Ready to Run flag. Remedy:
|
| Motor Overload Alarm |
Cause: Motor Protection Accumulator (04.019) in the drive has reached 75.0 % of the value at which the drive will trip and the load on the drive is >100 %. Remedy:
|
| Drive Overload Alarm |
Cause: Drive over temperature. Percentage Of Drive Thermal Trip Level (07.036) in the drive is greater than 90 %. Remedy:
|
| Auto Tune Alarm |
Cause: The autotune procedure has been initialized and an autotune in progress. Remedy:
|
How to Read H300 Faults via “Connect” Software
In 2026, the most effective way to troubleshoot complex HVAC systems is using the Control Techniques Connect PC software. This tool allows you to look past the keypad and see the drive’s internal logic in real-time.
- Dynamic Logic Diagrams: Connect allows you to visualize the drive’s control loops. You can see exactly why a “Feedback Loss” or “PI Loop Limit” might be preventing your fan from reaching speed.
- Trip History Log: The H300 stores the last 10 trips with precise timestamps from its Real-Time Clock (RTC). Navigate to Menu 10 in the software to view the log, including the DC bus voltage and current at the moment of the trip.
- Fire Mode Diagnostics: You can monitor Parameter 01.054 to see if a Fire Mode signal is overriding your Building Management System (BMS) commands.
- Drive Diagnostics App: For quick field work, use the smartphone app to scan the QR code on the drive’s front face. This will instantly pull up the “Possible Causes” and “Corrective Actions” for any active trip code.
Frequently Asked Questions (FAQ)
Q: What is the difference between an Alarm and a Trip on the H300?
A:
- Alarm (Alternating String): An indication like “Motor Overload” appears when the drive reaches 75% of its trip threshold. The motor keeps running, but you must act to prevent a shutdown.
- Trip (Solid Code): A protective shutdown. The drive stops the motor immediately and displays a code like OI.AC (Overcurrent).
Q: How do I reset an HVAC Drive H300 fault?
A: After clearing the root cause, you can reset the drive by:
- Pressing the Red STOP/RESET button on the HOA keypad.
- Cycling the Main Power (Wait for the display to turn off fully before reapplying power).
- Sending a reset command via the BACnet or Modbus network.
- Triggering a programmed Digital Input (Parameter 10.033).
Q: What does “Inhibit” mean on the display?
A: “Inhibit” (or inh) is a status, not a fault. It means the Safe Torque Off (STO) signal is missing from terminal 31 (or terminal 29 depending on frame size). The drive is healthy but is being prevented from running by an external safety circuit or E-Stop.
Q: My drive is in “Fire Mode.” Can I still stop it?
A: No. Once Fire Mode is triggered via a digital input, standard “Stop” commands from the keypad and BMS are overridden. The drive will continue to run until the Fire Mode signal is removed, the drive is destroyed, or the main power is cut. This is a life-safety requirement for smoke extraction fans.
Comments