INVT GD18 Drive Fault Codes List
Complete reference list of INVT Goodrive18 (GD18) fault codes. Learn to distinguish between P-Group (Unit 1) and F-Group (Unit 2) faults, troubleshoot 2-in-1 specific errors, and reset dual-motor systems.
INVT GD18 Fault Codes Reference Table
Use the search bar in the table below to quickly find your specific error code.
| Fault Codes | Cause & Solution |
| OC1 Overcurrent during acceleration |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC2 Overcurrent during deceleration |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC3 Overcurrent at constant speed |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OV1/OU1 Overvoltage during acceleration |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV2/OU2 Overvoltage during deceleration |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV3/OU3 Overvoltage at constant speed |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| UV Bus undervoltage |
Cause &
Solution: 1. An instantaneous power failure occurs. - Reset the fault 2. The AC drive's input voltage is not within the permissible range. - Adjust the voltage to normal range. 3. The bus voltage is abnormal. - Replace the AC drive. 4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal. - Replace the AC drive. |
| OL1 Motor overload |
Cause: - The voltage of the power supply is too low; - The motor setting rated current is incorrect; - The motor stall or load transients is too strong. Solution: - Check the power of the supply line; - Reset the rated current of the motor; - Check the load and adjust the torque lift. |
| OL2 VFD overload |
Cause: - The acceleration is too fast; - Reset the rotating motor; - The voltage of the power supply is too low; - The load is too heavy; - The motor power is too large, and the power of the VFD is too small. Solution: - Increase the ACC time; - Avoid the restarting after stopping; - Check the power of the supply line; - Select a VFD with bigger power; - Select a proper motor. |
| SPI Phase loss on input side |
Cause &
Solution: Phase loss or
violent fluctuation occurred to R, S, and T input. 1. Three phase input is abnormal. - Eliminate faults in external circuitry 2. Drive board is abnormal. - Eliminate faults in external circuitry 3. Lightning protection board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. 4. Control board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. |
| SPO Phase loss on output side |
Cause &
Solution: Phase loss occurred to U, V, W output (or the three phases of motor
is asymmetrical) 1. Motor winding is damaged. Check resistance between motor cables. - Replace motor is winding is damaged. 2. The cable connecting the AC drive and the motor is abnormal. - Check for wiring errors and ensure the output cable is connected properly 3. The AC drive's three-phase outputs are unbalanced when the motor is running. - Check whether the motor three-phase winding is normal. 4. The drive board or the IGBT is abnormal. - Replace the AC drive. |
| OH2 Inverter module overheat |
Cause &
Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. |
| EF External Fault |
Cause: SI external fault input terminals action. External fault
comes when the drive has detected an issue with an external control circuit
or device connected to it. This means the drive has detected an issue with an
external device or control circuit connected to it. Unlike error codes
specific to internal drive components, the EF code is more general and can be
triggered by various external factors. Solution: 1. An alarm function of the external equipment was activated. - Inspect external equipment operation. - Remove the cause of the alarm that occurred. 2. Connection has been performed incorrectly. - Check if the wire for the external alarm signal is correctly connected to the terminal to which the "Alarm from external equipment" has been assigned. - Connect the wire for the alarm signal correctly. 3. Incorrect settings. - Check if the "Alarm from external equipment" has not been assigned to an unassigned terminal. - Correct the assignment. |
| CE RS485 communication Fault |
Cause: - The baud rate setting is incorrect; - Fault occurs to the communication wiring; - The communication address is wrong; - There is strong interference to the communication. Solution: - Set proper baud rate; - Check the communication connection distribution; - Set proper communication address; - Chang or replace the connection distribution or improve the anti-interference capability. |
| ItE Current detection fault |
Cause: - The control panel connector is in poor contact; - An exception occurs on the magnifying circuit. Solution: - Check the connector and re-plug - Change the main control panel |
| tE Motor autotuning fault |
Cause: - The motor capacity does not comply with the VFD capability; - The rated parameter of the motor does not set correctly; - The offset between the parameters from autotuning and the standard parameter is huge; - Autotuning overtime. Solution: - Change the VFD mode; - Set the rated parameter according to the motor name plate; - Empty the motor load; - Check the motor connection and set the parameter; - Check if the upper limit frequency is above 2/3 of the rated frequency |
| EEP EEPROM operation fault |
Cause: - Error of controlling the write and read of the parameters; - Damage to EEPROM. Solution: - Press STOP/RST to reset; - Change the main control panel. |
| PIDE
PID feedback offline fault |
Cause: - PID feedback offline; - PID feedback source disappear. Solution: - Check the PID feedback signal; - Check the PID feedback source. |
| END Running time reached |
Cause: The actual running time of the VFD is above the internal
setting running time. Solution: Ask for the supplier and adjust the setting running time. |
| OL3 Electrical overload |
Cause: The VFD will report overload pre-alarm according to the set
value. Solution: Check the load and the overload pre-alarm threshold. |
| PCE Keypad communication error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Part of the communication circuits of the keypad or main board have fault. Solution: - Check the keypad cable and and ensure it is normal; - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service. |
| UPE Parameter upload error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Part of the communication circuits of the keypad or main board have fault. Solution: - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service; - Change hardware and ask for maintenance service. |
| DNE Parameter download error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Data storage error in keypad. Solution: - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service; - Back up data in the keypad again. |
| ETH1 To-ground short- circuit fault 1 |
Cause: - The output of the VFD is short circuited with the ground; - There is fault in the current detection circuit; - There is a great difference between the actual motor power setting and the VFD power. Solution: - Check if the connection of the motor is normal or not; - Change the hall; - Change the main control panel; - Reset the correct motor parameter; - Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| ETH2 To-ground short- circuit fault 2 |
Cause: - The output of the VFD is short circuited with the ground; - There is fault in the current detection circuit; - There is a great difference between the actual motor power setting and the VFD power. Solution: - Check if the connection of the motor is normal or not; - Change the hall; - Change the main control panel; - Reset the correct motor parameter; - Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| LL Electronic underload fault |
Cause: The VFD will report the underload pre-alarm according to the
set value. Solution: 1. Check the load and the underload pre-alarm point. |
| LInCE
LIN communication fault |
Cause: LIN communication fault time exceeds the timeout time. Solution: - In crease the LIN communication timeout time P/F14.17 to a greater value. - Change a new control board. |
| PoFF System power off |
Cause: System power off or low DC voltage. Solution: Check the grid. |
How to Read “Two-in-One” Fault Prefixes
The most critical aspect of troubleshooting the GD18 is identifying which drive unit is in fault. The LED display adds a prefix to the standard error code:
- P-Prefix (e.g., P-OC1): Indicates a fault on Inverter Unit 1 (Left Side / Motor 1).
- F-Prefix (e.g., F-OC1): Indicates a fault on Inverter Unit 2 (Right Side / Motor 2).
- Common Faults: Some system-level faults (like Keypad Communication PCE) may not have a prefix as they affect the entire control unit.
Advanced Diagnostics & History
To diagnose intermittent issues in 2026, you must look at the correct parameter group for the specific unit involved:
- Fault History:
- P07.27 – P07.32: Stores the last 6 faults for Unit 1.
- P07.33 – P07.40: Detailed operation data (Volts/Amps) at the moment of Unit 1’s last trip.
- Note: For Unit 2, refer to the corresponding Function Group (often mapped similarly but accessed via the “Unit Switch” (SHIFT) function on the keypad).
Frequently Asked Questions (FAQ)
Q: I see “P-OC1” and “F-OC1”. What is the difference?
A: Both codes indicate an Overcurrent during Acceleration.
P-OC1: Motor 1 is drawing too much current. Check the mechanical load or acceleration ramp time of the first motor.
F-OC1: Motor
2 is drawing too much current. These are independent systems; a fault
on one does not necessarily imply a problem with the other.
Q: How do I reset the drive if only one motor has tripped?
A: You can reset the specific unit in fault by:
1. Pressing the STOP/RST button on the keypad.
2.
Using the specific digital input assigned to “Fault Reset” for that
unit (e.g., S1 for Unit 1, S2 for Unit 2, depending on your P05
programming).
3. Cycling power to the entire unit.
Q: What does “SPI” mean on a GD18?
A: SPI stands for Input Phase Loss. Since both inverters share the same main power input (R, S, T), an SPI fault usually stops both motors.
Fix: Check the incoming power fuses, circuit breaker, and the tightness of the R/S/T terminal screws.
Comments
Post a Comment