INVT GD270 Drive Fault Codes List
Complete reference list of INVT GD270 (Fan & Pump) fault codes. Learn to troubleshoot HVAC specific errors like Dry Run, Pipe Broken, and PID feedback loss.
INVT GD270 Fault Codes Reference Table
Use the search bar in the table below to quickly find your specific error code.
| Fault Codes | Cause & Solution |
| OUt1 Inverter unit U phase protection |
Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OUt2 Inverter unit V phase protection |
Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OUt3 Inverter unit W phase protection |
Cause: 1. The acceleration is too fast; 2. IGBT module fault; 3. Misacts caused by interference; 4. The connection of the driving wires is not good; 5. Grounding is not properly. Solution: 1. Increase ACC time; 2. Change the power unit; 3. Check the driving wires; 4. Inspect external equipment and eliminate interference |
| OC1 Overcurrent during acceleration |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC2 Overcurrent during deceleration |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OC3 Overcurrent at constant speed |
Cause: - The acceleration or deceleration is too fast; - The voltage of the grid is too low; - The power of the VFD is too low; - The load transients or is abnormal; - The grounding is short circuited or the output is phase loss; - There is strong external interference; - The overvoltage stall protection is not open. Solution: - Increase the ACC time; - Check the input power; - Select the VFD with a larger power; - Check if the load is short circuited (the grounding short circuited or the wire short circuited) or the rotation is not smooth; - Check the output configuration; - Check if there is strong interference; - Check the setting of related function codes |
| OV1/OU1 Overvoltage during acceleration |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV2/OU2 Overvoltage during deceleration |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| OV3/OU3 Overvoltage at constant speed |
Cause: - The input voltage is abnormal; - There is large energy feedback; - No braking components; - Braking energy is not open. Solution: - Check the input power; - Check if the DEC time of the load is too short or the VFD starts during the rotation of the motor or it needs to increase the energy consumption components; - Install the braking components; - Check the setting of related function codes. |
| UV Bus undervoltage |
Cause &
Solution: 1. An instantaneous power failure occurs. - Reset the fault 2. The AC drive's input voltage is not within the permissible range. - Adjust the voltage to normal range. 3. The bus voltage is abnormal. - Replace the AC drive. 4. The rectifier bridge, the pre-charge resistor, the drive board or the control board are abnormal. - Replace the AC drive. |
| OL1 Motor overload |
Cause: - The voltage of the power supply is too low; - The motor setting rated current is incorrect; - The motor stall or load transients is too strong. Solution: - Check the power of the supply line; - Reset the rated current of the motor; - Check the load and adjust the torque lift. |
| OL2 VFD overload |
Cause: - The acceleration is too fast; - Reset the rotating motor; - The voltage of the power supply is too low; - The load is too heavy; - The motor power is too large, and the power of the VFD is too small. Solution: - Increase the ACC time; - Avoid the restarting after stopping; - Check the power of the supply line; - Select a VFD with bigger power; - Select a proper motor. |
| SPI Phase loss on input side |
Cause &
Solution: Phase loss or
violent fluctuation occurred to R, S, and T input. 1. Three phase input is abnormal. - Eliminate faults in external circuitry 2. Drive board is abnormal. - Eliminate faults in external circuitry 3. Lightning protection board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. 4. Control board is abnormal. - There is an hardware or software issue in drive. Need to repair or replace drive. |
| SPO Phase loss on output side |
Cause &
Solution: Phase loss occurred to U, V, W output (or the three phases of motor
is asymmetrical) 1. Motor winding is damaged. Check resistance between motor cables. - Replace motor is winding is damaged. 2. The cable connecting the AC drive and the motor is abnormal. - Check for wiring errors and ensure the output cable is connected properly 3. The AC drive's three-phase outputs are unbalanced when the motor is running. - Check whether the motor three-phase winding is normal. 4. The drive board or the IGBT is abnormal. - Replace the AC drive. |
| OH1 Rectifier module overheat |
Cause &
Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. |
| OH2 Inverter module overheat |
Cause &
Solution: 1. The ambient temperature is too high. - Lower the ambient temperature. 2. The ventilation is clogged. - Clean the ventilation. 3. The fan is damaged. - Replace the cooling fan. |
| EF External Fault |
Cause: SI external fault input terminals action. External fault
comes when the drive has detected an issue with an external control circuit
or device connected to it. This means the drive has detected an issue with an
external device or control circuit connected to it. Unlike error codes
specific to internal drive components, the EF code is more general and can be
triggered by various external factors. Solution: 1. An alarm function of the external equipment was activated. - Inspect external equipment operation. - Remove the cause of the alarm that occurred. 2. Connection has been performed incorrectly. - Check if the wire for the external alarm signal is correctly connected to the terminal to which the "Alarm from external equipment" has been assigned. - Connect the wire for the alarm signal correctly. 3. Incorrect settings. - Check if the "Alarm from external equipment" has not been assigned to an unassigned terminal. - Correct the assignment. |
| CE RS485 communication Fault |
Cause: - The baud rate setting is incorrect; - Fault occurs to the communication wiring; - The communication address is wrong; - There is strong interference to the communication. Solution: - Set proper baud rate; - Check the communication connection distribution; - Set proper communication address; - Chang or replace the connection distribution or improve the anti-interference capability. |
| ItE Current detection fault |
Cause: - The control panel connector is in poor contact; - An exception occurs on the magnifying circuit. Solution: - Check the connector and re-plug - Change the main control panel |
| tE Motor autotuning fault |
Cause: - The motor capacity does not comply with the VFD capability; - The rated parameter of the motor does not set correctly; - The offset between the parameters from autotuning and the standard parameter is huge; - Autotuning overtime. Solution: - Change the VFD mode; - Set the rated parameter according to the motor name plate; - Empty the motor load; - Check the motor connection and set the parameter; - Check if the upper limit frequency is above 2/3 of the rated frequency |
| EEP EEPROM operation fault |
Cause: - Error of controlling the write and read of the parameters; - Damage to EEPROM. Solution: - Press STOP/RST to reset; - Change the main control panel. |
| PIDE
PID feedback offline fault |
Cause: - PID feedback offline; - PID feedback source disappear. Solution: - Check the PID feedback signal; - Check the PID feedback source. |
| bCE Braking unit fault |
Cause: - Braking circuit fault or damage to the braking pipes; - The external braking resistor is not sufficient. Solution: - Check the braking unit, and change new braking pipe; - Increase the braking resistor. |
| END Running time reached |
Cause: The actual running time of the VFD is above the internal
setting running time. Solution: Ask for the supplier and adjust the setting running time. |
| OL3 Electronics overload |
Cause: The VFD will report overload pre-alarm according to the set
value. Solution: Check the load and the overload pre-alarm threshold. |
| PCE Keypad communication error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Part of the communication circuits of the keypad or main board have fault. Solution: - Check the keypad cable and and ensure it is normal; - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service. |
| UPE Parameter upload error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Part of the communication circuits of the keypad or main board have fault. Solution: - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service; - Change hardware and ask for maintenance service. |
| DNE Parameter download error |
Cause: - The keypad is not in good connection or offline; - The keypad cable is too long and there is strong interference; - Data storage error in keypad. Solution: - Check the environment and eliminate the interference source; - Change hardware and ask for maintenance service; - Back up data in the keypad again. |
| ETH1 To-ground short- circuit fault 1 |
Cause: - The output of the VFD is short circuited with the ground; - There is fault in the current detection circuit; - There is a great difference between the actual motor power setting and the VFD power. Solution: - Check if the connection of the motor is normal or not; - Change the hall; - Change the main control panel; - Reset the correct motor parameter; - Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| ETH2 To-ground short- circuit fault 2 |
Cause: - The output of the VFD is short circuited with the ground; - There is fault in the current detection circuit; - There is a great difference between the actual motor power setting and the VFD power. Solution: - Check if the connection of the motor is normal or not; - Change the hall; - Change the main control panel; - Reset the correct motor parameter; - Check whether motor power parameters in P2 group is consistent with the motor power actually used. |
| dEu Speed deviation fault |
Cause: Load is too heavy, or stall occurred. Solution: - Check the load to ensure it is proper, increase the detection time. - Check whether control parameters are set properly. |
| STo Maladjustment fault |
Cause: - Control parameters of synchronous motor is set improperly; - The parameter gained from autotuning is inaccurate; - The VFD is not connected to motor Solution: - Check the load to ensure it is proper, - Check whether load is proper; - Check whether control parameters are set correctly; - Increase maladjustment detection time |
| LL Electronic underload fault |
Cause: The VFD will report the underload pre-alarm according to the
set value. Solution: 1. Check the load and the underload pre-alarm point. |
| OT Motor over temperature |
Cause: Motor over-temperature input terminal is valid. - Exception occurred to t temperature detection Exception occurred to resistor. - Long-time overload running or exception occurred. Solution: - Check the wiring of motor over-temperature input terminal. - Check whether temperature sensor is proper; - Check the motor and perform maintenance on the motor |
| E-Err
Repetitive expansion card type |
Cause: The two inserted expansion cards are of the same type. Solution: - You should not insert two cards with the same type; - Check the type of expansion card, and remove one card after power down. |
| F1-Er Failed to identify the expansion card in card slot 1 |
Cause: There is data transmission in interfaces of card slot 1,
however, it cannot read the card type. Solution: - Confirm whether the expansion card inserted can be supported; - Stabilize the expansion card interfaces after power down, and confirm whether fault still occurs at next power-on; - Check whether the insertion port is damaged, if yes, replace the insertion port after power down |
| F2-Er Failed to identify the expansion card in card slot 2 |
Cause: There is data transmission in interfaces of card slot 2,
however, it cannot read the card type. Solution: - Confirm whether the expansion card inserted can be supported; - Stabilize the expansion card interfaces after power down, and confirm whether fault still occurs at next power-on; - Check whether the insertion port is damaged, if yes, replace the insertion port after power down |
| C1-Er Communication timeout occurred to the expansion card in card slot 1 |
Cause: There is no data transmission in interfaces of card slot
1. Solution: - Confirm whether the expansion card inserted can be supported; - Stabilize the expansion card interfaces after power down, and confirm whether fault still occurs at next power-on; - Check whether the insertion port is damaged, if yes, replace the insertion port after power down. |
| C2-Er
Communication timeout occurred to the expansion card in card slot 2 |
Cause: There is no data transmission in interfaces of card slot
2. Solution: - Confirm whether the expansion card inserted can be supported; - Stabilize the expansion card interfaces after power down, and confirm whether fault still occurs at next power-on; - Check whether the insertion port is damaged, if yes, replace the insertion port after power down |
| E-DP PROFIBUS card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped. |
| E-NET Ethernet card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller. Solution: - Check whether the communication card wiring is loose or dropped. |
| E-CAN CANopen card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped. |
| E-PN PROFINET card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped. |
| E-CAT EtherCAT card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped. |
| E-BAC BACNet card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped. |
| E-DEV DeviceNet card communication timeout fault |
Cause: There is no data transmission between the communication card
and the host controller (or PLC). Solution: - Check whether the communication card wiring is loose or dropped |
| SECAN CAN master/slave communication card communication timeout fault |
Cause: There is no data transmission between the CAN master and
slave communication cards. Solution: - Check whether the communication card wiring is loose or dropped. |
| S-Err CAN slave fault in master/slave synchronization |
Cause: Fault occurred to one of the CAN slave VFDs. Solution: - Detect the CAN slave VFD and analyze the corresponding fault cause of the VFD. |
| FrOST Freezing fault |
Cause: The temperature is lower than the freezing protection
threshold. Solution: - Check the temperature. |
| BLOCK Stalling fault |
Cause: The current is greater than the stalling current. Solution: - Check for stalling. |
| Dr Dry pumping |
Cause: The current is lower than the current limit for motor dry
pumping. Solution: - Check for dry pumping. |
| PoFF System power off |
Cause: System power off or low DC voltage. Solution: Check the grid. |
Troubleshooting Pump & Fan Specific Faults
Because the GD270 manages fluid systems, it offers advanced diagnostics that go beyond the VFD hardware.
- Application Protection Logs: The GD270 monitors system pressure and flow. It can trigger alarms for Dry Run (Load Loss) or Pipe Breakage (PID deviation). These are not drive failures but system warnings.
- RTC (Real Time Clock) Timestamping: The GD270 often comes with an LCD keypad featuring a real-time clock. Faults are recorded with the exact Date and Time, making it easier to correlate trips with external events (e.g., shifts in water demand).
- Multi-Pump Status: If running in a multi-pump cascade mode, use parameter group P90 to check the communication status between the master and slave drives to diagnose synchronization errors.
Frequently Asked Questions (FAQ)
Q: What does the “LL” (Electronic Overload / Load Loss) code mean?
A: In the context of the GD270, LL often indicates a Dry Run condition (Underload). The pump is running but drawing very little current because there is no water/air resistance.
Fix: Check
the inlet water supply, check for airlocks in the pump, or adjust the
underload detection threshold in the protection parameters.
Q: How do I fix “PIDE” (PID Feedback Loss)?
A: This occurs when the drive expects a signal from
your pressure transducer or flow meter (4-20mA or 0-10V) but detects a
wire break.
Troubleshooting:
1. Check the wiring at the analog input terminals (AI1/AI2).
2. Measure the sensor output with a multimeter.
3. Verify the “Feedback Loss Action” setting (usually in Group P40 or P08).
Q: The drive trips on “OL2” (Motor Overload) only at certain times of day. Why?
A: This is common in pump applications during peak demand.
1. Check if the pump is sized correctly for the maximum head required.
2. Ensure the “Pump Cleaning” or “Anti-Jam” function is not triggering unnecessarily.
3.
If driving a Permanent Magnet (PM) motor, ensure the back-EMF
parameters are correctly tuned, as a mismatch causes high current draw.