bP Warning in delta VJ series Drive

bP Warning in delta VJ series Drive

How can resolve problem bP Warning in delta VJ series Drive ?

The function of this warning code is to prevent oil pump from
damaging while running without sucking in any hydraulic oil.
When the hybrid servo drive goes from STOP to RUN, it starts
to check if the pressure is over 0.5Bar within the time set at
Pr.00-60. During this checking period, the servo drive refuses
pressure command and flow command sent from keypad. The
keypad displays bp (building pressure).
If the pressure is still under 0.5bar after the checking period
set at Pr.00-60, there will be an oil shortage warning and the
hybrid servo drive will stop running. The keypad will display
noil (no oil).
If the pressure is over 0.5bar within the checking time set at
Pr00-60, the hybrid servo drive continues to run normally.
There won’t be a bp warning. (bP)
※ This function is effective when Pr.00-27 <minimum pressure> is
set as higher than 0.3% and the time setting at Pr.00-60
is NOT 0

click here for more information



Comments

Popular posts from this blog

3210 DC bus overvoltage fault in lenze i550 drive

Fault 3381 in ABB ACS560 Drive

Fault 3181 in ABB ACS560 Drive