Err02 fault in Emotron VS Series Drive
Err02 fault indicates Decel overcurrent. This means the inverter's output current has exceeded the safe threshold during the motor's deceleration phase.
Possible Causes:
1: The output circuit is grounded or short circuited.
2: The deceleration time is too short.
3: The voltage is too low.
4: A sudden load is added during deceleration.
5: The braking unit and braking resistor are not installed.
Solutions:
1: Eliminate external faults.
2: Increase the deceleration time.
3: Adjust the voltage to normal range.
4: Remove the added load.
5: Install the braking unit and braking resistor.