Err05 fault in Emotron VS Series Drive

Err05 fault indicates Decel overvoltage. This means the drive's internal DC bus voltage has risen above the maximum safe limit during motor deceleration. Possible Causes: 1: The input voltage is too high. 2: An external force drives the motor during deceleration. 3: The deceleration time is too short. 4: The braking unit and braking resistor are not installed. Solutions: 1: Adjust the voltage to normal range. 2: Cancel the external force or install the braking resistor. 3: Increase the deceleration time. 4: Install the braking unit and braking resistor.