Err08 fault in Emotron VS Series Drive

Err08 fault indicates Short circuit. This means there is an abnormally high current flow due to a direct connection between phases or to ground, bypassing the normal load. Possible Causes: 1: The output circuit is grounded or short circuited. 2: The connecting cable of the motor is too long. 3: The module overheats. 4: The internal connections become loose. 5: The main control board is faulty. 6: The drive board is faulty. 7: The inverter module is faulty. Solutions: 1: Eliminate external faults. 2: Install a reactor or an output filter. 3: Check the air filter and the cooling fan. 4: Connect all cables properly. 5: Contact the agent or CG.