F0022 fault in WEG CFW500 Drive

F0022 fault in WEG CFW500 Drive indicates Overvoltage on the DC Link. This means the internal DC bus voltage has spiked too high, typically caused by rapid deceleration of a high-inertia load. 

Cause:


  • Wrong voltage supply (comply with inverter rating plate and parameter P0296).
  • DC link voltage exceeded permissible limits (monitored in P0004):
    • Ud > 410 Vdc in 200-240 Vac (P0296 = 0).
    • Ud > 810 Vdc in 380-480 Vac (P0296 = 1).
    • Ud > 1000 Vdc in 500-600 Vac (P0296 = 2).
  • Load inertia is too high or deceleration ramp is too fast.
  • Parameters P0151, P0153, or P0185 are set too high.


Remedy:

Verify incoming mains supply. Increase deceleration time. Adjust parameters P0151, P0153, or P0185.