F7412 fault in Siemens V70 Drive

F7412 fault in Siemens V70 Drive indicates an incorrect Commutation angle. This means the drive cannot correctly determine the rotor's magnetic position, often caused by a misaligned or damaged motor encoder. Cause: An incorrect commutation angle was detected that can result in a positive coupling in the speed controller.
Possible causes:
  • The motor encoder is incorrectly adjusted with respect to the magnet position.
  • The motor encoder is damaged.
  • Data to calculate the motor model has been incorrectly set.
  • Pole position identification might have calculated an incorrect value when activated.
  • The motor encoder speed signal is faulted.
  • The control loop is unstable due to incorrect parameterization.

Remedy:
  • If the encoder mounting was changed, re-adjust the encoder.
  • Replace the defective motor encoder.
  • Correctly set the motor stator resistance, cable resistance and motor-stator leakage inductance. Calculate cable resistance from cross-section/length. Check inductance/stator resistance using motor data sheet. Measure stator resistance (e.g. multimeter).
  • With pole position identification activated, check the procedure and force a new identification procedure by means of deselection followed by selection.