oL2 fault in Emotron VSB Drive
oL2 fault indicates Motor overloaded. This means the motor is drawing current exceeding its rated capacity, triggering the drive's thermal protection algorithm for the motor.
Possible Causes:
1: Torque boost is too big under V/f control.
2: Inappropriate V/f curve under V/f control.
3: Motor parameters are improperly set.
4: Improper setting of motor overloaded protection time.
5: Motor stalled or sharp variation of load.
6: Long-term running of ordinary motor at low speed with heavy load.
Solutions:
1: Reduce torque boost value.
2: Set V/f curve correctly.
3: Set the parameters correctly according to motor nameplate.
4: Properly set the motor overloaded protection time.
5: Identify the causes of motor stalling or check the load condition.
6: Select variable frequency motor.