ov2 fault in Emotron VSB Drive
ov2 fault indicates Constant-speed overvoltage. This means the inverter's internal DC bus voltage exceeded the safe limit while the motor was operating at a steady, constant speed.
Possible Causes:
1: Load variation is too big.
2: Abnormal input voltage.
3: Output short circuit (phase-to-phase short circuit or output ground short circuit).
4: Improper parameter setting of regulator under SVC control.
Solutions:
1: Check the load.
2: Check power grid voltage.
3: Check motor connection and output ground impedance.
4: Properly set regulator parameters.