A0134 fault in WEG CFW500 Drive
A0134 alarm in WEG CFW500 Drive indicates a Bus Off condition on the CAN interface. This means the network experienced too many data errors and isolated itself from the bus to prevent further issues.
Cause:
Remedy:
Check CAN high and low wires for short circuits or inverted signals. Match node baud rates across the network. Check termination resistor values and placement.
Cause:
- Short circuit on the CAN circuit transmission cable.
- CAN cables are misconnected or inverted.
- Mismatched baud rates among network devices.
- Termination resistors with the right value were not installed correctly (should only be at the physical ends of the main bus).
- CAN network was improperly installed.
Remedy:
Check CAN high and low wires for short circuits or inverted signals. Match node baud rates across the network. Check termination resistor values and placement.